Raychem ETS-05 electronic thermostat

Overview

The Raychem ETS-05 electronic surface sensing thermostat provides accurate temperature control for heating cables. It is available in two versions. Fitted with a flexible sensor and mounted on a pipe stand, the ETS-05-Lx-A KIT monitors temperatures of up to 199°C (390°F) while the wall-mountable ETS-05-Hx-A can be used for temperatures of up to 499°C (930°F).
The maximum nominal load is 24A for both thermostats. The temperature setting is set accurately via digital rotary switches inside the enclosure.

The ETS-05 has a LED indicator which indicates the status of the thermostat (powered on/off), the status of the heat-tracing cable (powered on/off) and the status of the temperature sensor. In case of sensor failure, the thermostat can switch to an on or off state, depending upon the user’s requirement.

Technical Specifications

Area of useHazardous area: Zone 1 or Zone 2 (Gas) or Zone 21 (Dust) CL I, DIV 2 Ordinary Locations
Ambient temperature-40°C to +60°C(–40°F to + 140°F)
Switching capacity24 A resistive load
Terminal size6mm2
Temperature range and sensorETS-05 -Lx-A: 0°C to 199°C (32°F to 390°F)with flexible sensor
ETS- 05 -Hx-A: 0°C to 499°C (32°F to 930°F)
Fail SafeProgrammable fail safe on and fail safe off at sensor failure or sensor wire shortcut.
Inspired Solutions for a Changing World